+
expand all
This could mean one of two things.
1. An intermittent chirp is probably an indication of a defective smoke detector.
2. A consistent chirp is probably an indication of a low battery condition and the smoke detector requires a new battery.
This is usually caused by several factors.
1. Use of non-brand named bulbs.
2. Larger wattage bulbs, which cause excessive heat build-up shorting the life of the bulb.
3. Power Surges.
4. Heat can build up causing damage to the socket and wires.
Please remember if you have a problem with your phone wiring within your home, today it is the responsibility of the electrician rather than the phone company as in the past.
With deregulation of the utility companies in most areas of the country, the cable or telephone companies are no longer responsible for the equipment or wiring in your home. This responsibility has fallen to you and your electrical contractor. Therefore, when a problem arises, we recommend you us. Most TV and telephone utilities will still service within your home for a substantial fee. This service, as in the past, is no longer free.
Modern Recess Cans are rated for a maximum wattage bulb and are equipped with a thermal device that does not allow a bulb larger than that rating. If a larger wattage bulb is used, as the excess heat builds up, the thermal device will shut the can off until it cools. This is a safety device to protect your home against fire.
Yes. Within reason, if the quantity of lights creates a load greater than the capacity of the circuit breaker, the breaker will trip off. In this event, additional circuits may be required to accommodate your holiday display. Also, in addition to that they need to make sure any exterior outlets plugged into anytime should be gfci protected and inspect light stands for cuts or nicks in wire that will cause GFCI to trip especially when wet, and also tape up empty or missing light sockets and change broken lamps.
Yes. Main line surge is no absolute guarantee and any additional surge protection down stream in the system offers a greater level of protection; though, nothing is absolute when it comes to the power of Mother Nature.
No. Surge/Lightning Protection only offers additional levels of protection. Nothing can guarantee completely against Mother Nature and where she chooses to strike.
Yes. This is a common occurrence when large motor/compressor loads start. These devices cause a minor momentary voltage drop, demonstrating itself as the blinking in your lights. This has no negative effect on the electrical equipment within your house.
Yes temporary... but keep in mind that any larger loads of appliances should be on a dedicated line to prevent added stress to line or steady exposure of high loads across branch circuits or multiple connection. This will increase the connections chances of failing and with multiple openings or connections on a branch circuit will increase your probability of a problem or possibly a fire. Some larger loads that should have there own dedicated line are heating or cooling devices such as heaters, microwaves, blow dryers, irons, coffee pots, fridge or freezer, Window units, dishwashers, hot tubs... etc.
Yes, Kitchen counter top circuits should have a minimum 2 - 20A 120v circuits just on outlets which will handle heavy loads, some wiring methods distribute power differently but it maybe that this is too much load for the circuit at one time and in this event you would have to limit use of devices to one at a time, relocate one device, or add an additional circuit to better accommodate your load needs.
Unless you made provisions with the builder for a dedicated circuit, the outlets in your garage are GFCI Protected per National Electrical Code. This device will not tolerate the additional resistance load created by refrigeration equipment. The GFCI senses there is a fault, and therefore trips off. The only cure to this problem is to provide a dedicated, non-GFCI circuit allowable by code.
Yes. Dimming fluorescent requires not only a special dimmer, but also special fixtures. You cannot place a typical incandescent dimmer on existing fluorescent.
Yes, but first you must make sure the electrical box is properly braced and rated for the weight and torque of the ceiling fan you are installing.
Flickering may indicate impending bulb failure, minor power fluctuation, and/or improperly installed bulbs. Cycling on and off is usually a clear indication of ballast and/or bulb failure. It is recommended when replacing a ballast to replace bulbs as well.
First, disconnect any additional devices that may have caused the breaker to overload and trip. Breakers are mechanical devices and must be turned all the way off before turning back on. Remember this is a mechanical device, so this may require several attempts. If this fails to reset the breaker, there may be a more serious problem. Call CR Electric Services (504) 737-6024.
Check to see if the outlet is on a switch. Check and reset GFCI outlets and circuit breaker. Check light bulbs and replace if necessary. If none of these are the problem, call CR Electric Services (504) 737-6024.
Except in the case of ground fault interrupters, which are susceptible to moisture and/or weather conditions, fuses and circuit breakers should not trip. Check to see if some type of plugged in appliance is causing the problem.
GFCI stands for Ground Fault Circuit Interrupter. In layman's terms this device protects you from electrical shock. When it senses the slightest increase in resistance resulting from ground fault, (i.e., the use of electrical devices in or near water), it turns off to protect you.
Central air conditioning and heat pump condensers may cause a noticeable slight dimming on start up. Lights may flicker or dim due to startup of some appliances or motor driven equipment. Check with the local utility company for possible defects in supply source or for the utility switching to other utilities for supply.